Check out the Zoeller YouTube Channel for tips, training, and product videos!

X

Pivot Pro+ Series


Pivot Pro+ Series

Application- Commercial Buildings

Pivot Pro+ panels are built the same as Pivot Pro panels but in larger enclosures. This  larger enclosure allows for variations such as Reversing panels, Start Kit panels, and other future variations.

Certifications

  • cCSAus certified to standard UL508
  • FCC Class-B certification to ISED Canada ICES-003, Issue 6
  • For outdoor or indoor use,-40 ˚F to +140 ˚F (-40 ˚C to +60 ˚C)

Components

  • Red alarm beacon with 360˚ visibility
  • Audible alarm buzzer rated 95 db at 2’ (0.6 m)
  • SILENCE/RESET/TEST toggle switch with weatherproof rubber boot
  • HAND/OFF/AUTO control are included for each pump
  • RS-485 (12VDC, 2W) powered serial port for optional Z Control® Gateway connectivity
  • Auxiliary output dry contacts (NO-COM-NC) terminals, Form C, 5A resistive load
  • PUMP RUN dry contact, (NO-COM)
  • NEMA 4X 14”x12”x6” enclosure with lockable latch
  • Reversing and Start Kit panels contain additional required hardware

Power

  • Control circuit powered by 120VAC, 60 Hz
  • Alarm circuit can be powered by separate power feed, if needed
  • Alarm and control circuits individually fused, 3A, fast-acting, 120VAC
  • Circuit breaker protection on 1Ph models
  • Multi-tap 200/230/460V transformer on 3Ph models
  • Max alarm and control circuit power consumption: Simplex models 32W, Duplex models 40W
  • Max standby power consumption: 5W
  • Terminals for 120VAC control power, 120VAC alarm power, up to 4 float switches (duplex), pump input power
  • 1Ph IEC motor contactors, models 120/208/240 VAC, 50/60Hz, up to 50A maximum
  • 3PH IEC motor contactors, models 208/230/380/460/575 VAC, 60Hz

Field Wiring & Maintenance

  • 4 enclosure mounting brackets are included
  • 2 sets of wiring schematics and installation instructions are included along with an inside door mounted QR code for easy access to additional support material online
  • All wires and terminal locations thoroughly labeled for easy identification
  • All components are serviceable (See FM3364 for available replacement parts)